USER’S GUIDE
Managed Rack PDU
65
olOnDelay
Access: Administrator, Device User, and Outlet User, but only for outlets to which the
user is assigned.
Description: Set or view the time delay for the On Delayed command (see olDlyOn)
and for a Reboot Delayed command (see olDlyReboot).
Example 1: To set a 6-second delay for turning on outlets 3 and 5 through 7, type:
cli> olOnDelay 3,5-7 6
E000: Success
Example 2: To view the delay for the On Delayed command for outlets 3 and 5 through
7, type:
cli> olOnDelay 3,5-7
E000: Success
3: BobbysServer: 6 sec
5: BillysServer: 6 sec
6: JoesServer: 6 sec
7: JacksServer: 6 sec
Argument Description
all All device outlets.
<outlet
name>
The name configured for a specific outlet. (See olName.)
<outlet#> A single number or a range of numbers separated with a
dash, or a comma-separated list of single outlet numbers
and number ranges.
<time> A time for the delay within the range of 1 to 7200 seconds
(2 hours).