USER’S GUIDE
Managed Rack PDU
23
Example of a command that accepts mutually exclusive arguments for an
option:
alarmcount -p [all | warning | critical]
In this example, the option -p accepts only three arguments: all, warning, or critical. For
example, to view the number of active critical alarms, type:
alarmcount -p critical
The command will fail if you type an argument that is not specified.
Command Response Codes
The command response codes enable scripted operations to detect error conditions
reliably without having to match error message text:
The CLI reports all command operations with the following format:
E [0-9] [0-9] [0-9] : Error Message
Code Message Code Message
E000 Success E105 Command Prefill
E001 Successfully Issued E106 Data not available
E002 Reboot required for
change to take effect
E107 Serial communication
with the Rack PDU has
been lost
E100 Command failed
E101 Command not found
E102 Parameter error
E103 Command line error
E104 User level denial