Dell PowerEdge FX2 and FX2s Enclosure
Owner's Manual
Regulatory Model: E24S
Regulatory Type: E24S001
Vista de página 0
1 2 3 4 5 6 ... 94 95

Resumo do Conteúdo

Página 1 - Owner's Manual

Dell PowerEdge FX2 and FX2s EnclosureOwner's ManualRegulatory Model: E24SRegulatory Type: E24S001

Página 2 - Notes, cautions, and warnings

Item Indicator, Button, or ConnectorIcon Description4 KVM select button Enables you to map the KVM to the sleds.5 Sleds PowerEdge FX2/FX2s supports up

Página 3 - Contents

Health indicatorElectrical indicatorCondition Corrective ActionThe indicator blinks amber if the system experiences an electrical error (for example,

Página 4

Powering off the chassis and sledsFor a graceful shutdown of all the sleds and the chassis, press and hold the chassis power button for 4 to 10 second

Página 5

Figure 8. Back panel features and indicators—PowerEdge FX2Item Indicator, Button, or ConnectorDescription1 Serial connector DB-9 serial connector for

Página 6 - Terms used in the document

Item Indicator, Button, or ConnectorDescription8 I/O module (2) Provides Ethernet connectivity to the compute sleds in the enclosure.9 I/O module port

Página 7

ConventionPower indicator patternConditionCAUTION: When correcting a PSU mismatch, replace only the PSU with the flashing indicator. Swapping the oppo

Página 8 - Sled slot numbering

Indicator DescriptionStatus indicatorBlue The I/O module is operating normally.Blinking Blue The CMC is identifying the I/O module.Blinking Amber The

Página 9

– Supports setting an optional enclosure Maximum Power Limit, which either alerts or takes actions, such as throttling compute sleds and/or preventing

Página 10 - Diagnostic indicators

Figure 12. CMC daisy-chaining1. management network 2. CMCCooling fan indicator codesEach cooling fan has an LED that indicates the power status of the

Página 11 - Power button functions

Figure 13. Cooling fan indicators1. status indicatorConfiguration wizardThe CMC is pre-configured to use a static IP address. To use Dynamic Host Conf

Página 12 - KVM features

Notes, cautions, and warningsNOTE: A NOTE indicates important information that helps you make better use of your computer.CAUTION: A CAUTION indicates

Página 13

Documentation matrixThe documentation matrix provides information about documents that you can refer to, for setting up and managing your system.To...

Página 14 - Power supply unit indicators

To... Refer to...Know the features of the storage controller cards, deploy the cards, and manage the storage subsystemStorage controller documentation

Página 15 - I/O module indicators

2Initial system configurationBefore you beginCAUTION: The enclosure power supplies must be connected to a PDU or to an electrical outlet. The power su

Página 16 - CMC module

• Connect to one of the compute sleds and boot to the Human Interface Infrastructure (HII) browser to retrieve the CMC IP address.10. Connect to the C

Página 17

3PowerEdge FX2/FX2s mapping configurationsThis section provides the following information on the connectivity of the compute sleds to the I/O module(s

Página 18 - Cooling fan indicator codes

– To establish optical links between two 10 Gb pass-through modules, an external rack switch must be used as an intermediary. Direct optical connectio

Página 19 - Configuration wizard

Figure 17. I/O module port mapping—half-width compute sleds with quad port NDC/network outputA half-width compute sled configured with quad-port NDC i

Página 20 - Documentation matrix

The following table lists the compute sleds and the ports to which they are mapped.Table 4. I/O module port mapping in eight-bay chassisCompute sled I

Página 21 - Quick Resource Locator

Table 5. I/O module port mapping in a six-bay chassisCompute sledIO Module A1 (Top) IO Module A2 (Bottom)1a 1 11b 2 21c 3 31d 4 43 5, 6 (for half-widt

Página 22 - Initial system configuration

In the three-bay chassis, a full-width compute sled is mapped to four ports on each I/O module. A half-width compute sled with quad port NDC is mapped

Página 23 - Logging in to the CMC

Contents1 About your Dell PowerEdge FX2/FX2s...6Terms used in the document...

Página 24 - PowerEdge FX2/FX2s mapping

Manual at dell.com/poweredgemanuals. The PCIe mezzanine cards are mapped to the PCIe expansion slots on the enclosure. For more information, see PCIe

Página 25

• Four-bay chassis—Each half-width compute sled is mapped to two PCIe slots.• Eight-bay chassis—Each quarter-width compute sled is mapped to one PCIe

Página 26

Figure 24. Compute sled to PCIe slot mapping—six-bay chassisFigure 25. Compute sled to PCIe slot mapping—two-bay chassisFigure 26. Compute sled to PCI

Página 27

feature applies to enclosure configurations with or without storage sleds. You can enable or disable the PCIe reassignment option by using the CMC web

Página 28

Figure 29. PCIe slot mapping from compute sled mapped to storage sleds—three-bay chassisFigure 30. PCIe slot mapping from compute sleds mapped to stor

Página 29

4Installing and removing PowerEdge FX2/FX2s enclosure componentsThis section provides information on installing and removing the enclosure components.

Página 30 - Expansion bus

CAUTION: Do not operate the system without the cover for a duration exceeding three minutes.CAUTION: Many repairs may only be done by a certified serv

Página 31

NOTE: To ensure proper operation and cooling, replace the system cover within three minutes of removal.1. Ensure that you read the Safety instructions

Página 32

Steps1. Place the bottom edge of the cover, opposite the cover lock, into the slots on the system.2. Lower the cover onto the system.3. Slide the syst

Página 33

Figure 32. Removing and installing a compute sled1. enclosure 2. compute sled3. compute sled handle 4. release button on sled handleNext stepsInstall

Página 34 - Internal management network

4 Installing and removing PowerEdge FX2/FX2s enclosure components...

Página 35 - FX2s enclosure components

3. Align the compute sled with the bay in the enclosure.4. Slide the sled into the enclosure until the sled connectors are firmly engaged with the mid

Página 36 - System cover

Figure 33. Removing a storage sled1. sled lock (2) 2. dotted line on storage sled3. sled release latch (2)Figure 34. Removing and installing the I/O c

Página 37 - Installing the system cover

Installing a storage sledInstalling a storage sledPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should on

Página 38 - Removing a compute sled

Figure 35. Installing a storage sled1. dotted line on storage sled 2. sled lock (2)Next stepsTurn on the compute sled(s) to which the storage sled is

Página 39 - Installing a compute sled

Figure 36. Inside the system—PowerEdge FX2s1. midplane 2. fan (8)3. power bus bar 4. power interposer board5. PSU (2) 6. PCIe module (8)7. CMC moduleN

Página 40 - Removing a storage sled

CMC moduleYour system supports a hot-swappable CMC module that provides multiple systems management functions.Removing the CMC modulePrerequisitesCAUT

Página 41

Installing the CMC modulePrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshootin

Página 42 - Installing a storage sled

Figure 38. Removing and installing a CMC module SD card1. SD card 2. SD card connectorNext stepsInstall the CMC module and reattach any cables that we

Página 43 - Inside the system

Figure 39. Removing and installing an I/O module1. I/O module 2. I/O module handle3. release latchNext stepsInstall the I/O module.Related LinksInstal

Página 44

Removing a PCIe modulePrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshooting a

Página 45

Removing the PCIe switch board...59Installing the PCIe s

Página 46 - Installing the CMC module

Installing a PCIe modulePrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshooting

Página 47 - I/O module

Expansion card operational power statusThe following table provides information on the operational power status of expansion cards when they are insta

Página 48 - PCIe module

Removing an expansion cardPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshooti

Página 49 - Removing a PCIe module

Next steps1. Install the PCIe module.2. Turn on the compute sled to which the expansion card is mapped.Related LinksRemoving a PCIe moduleInstalling a

Página 50 - Expansion cards

Removing a power supply unitPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshoo

Página 51 - PCIe module indicators

Installing a power supply unitPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troublesh

Página 52 - Removing an expansion card

WARNING: The cooling fan can continue to spin for some time after it has been powered down. Allow time for the fan to stop spinning before removing it

Página 53 - Power supply units

3. cooling fan (8)Next stepsInstall the cooling fan.Related LinksInstalling a cooling fanRemoving the system coverInstalling a cooling fanPrerequisite

Página 54 - Removing a power supply unit

1. Ensure that you read the Safety instructions.2. Follow the procedure listed in Before working inside your system.3. Remove the system cover.4. Remo

Página 55 - Cooling fans

Removing the system coverRemoving a cooling fanInstalling the cooling-fan cagePrerequisitesCAUTION: Many repairs may only be done by a certified servi

Página 56

1About your Dell PowerEdge FX2/FX2sThe Dell PowerEdge FX2/FX2s is a 2U enclosure that can support up to four half-width compute sleds, up to eight qua

Página 57 - Cooling-fan cage

NOTE: This is a field replaceable unit (FRU). Removal and installation procedures must be performed only by Dell certified service technicians.NOTE: Y

Página 58

Removing a cooling fanRemoving the cooling-fan cageRemoving a PCIe moduleInstalling the PCIe switch boardPrerequisitesCAUTION: Many repairs may only b

Página 59 - PCIe switch board

Removing the fan interface boardPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform trouble

Página 60

3. spring-loaded screw (2)Next stepsInstall the fan interface board.Related LinksInstalling the fan interface boardRemoving the system coverRemoving a

Página 61 - Fan interface board

Interposer moduleThe interposer module allows you to install quarter-width sleds in the PowerEdge FX2/FX2s enclosure that comes pre-installed with hal

Página 62

Removing the bottom interposer modulePrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform tr

Página 63

Figure 49. Removing and installing screws securing the bottom partition1. bottom of the system 2. screw (5)b. Remove the two screws that secure the bo

Página 64 - Interposer module

Figure 51. Removing and installing the bottom partition1. bottom partition 2. screw (2)6. Remove the two screws that secure the bottom interposer modu

Página 65

Removing a storage sledRemoving a power supply unitRemoving the CMC moduleRemoving an I/O moduleRemoving a PCIe moduleRemoving the system coverRemovin

Página 66

2. Follow the procedure listed in After working inside your system.Related LinksRemoving the bottom interposer moduleInstalling the cooling-fan cageIn

Página 67

Term DescriptionFour-bay chassis Refers to the PowerEdge FX2/FX2s enclosure configuration that supports up to four half-width compute sleds.NOTE: In P

Página 68

Figure 53. Removing and installing screws securing the top partition to the middle plate1. middle plate 2. bottom of the system3. screw (3)b. Remove t

Página 69

Figure 55. Removing and installing the top partition1. top partition 2. screw (3)6. Remove the two screws that secure the top interposer module to the

Página 70

Removing a compute sledRemoving a storage sledRemoving a power supply unitRemoving the CMC moduleRemoving an I/O moduleRemoving a PCIe moduleRemoving

Página 71

• CMC module• power supplies• sleds2. Follow the procedure listed in After working inside your system.Related LinksRemoving the top interposer moduleI

Página 72

• interposer module(s), if applicableSteps1. Remove the two fan cables connected to the midplane.2. Remove the two screws that secure the fan cable cl

Página 73 - Midplane assembly

7. power interposer board Next steps1. Install the midplane assembly.Related LinksInstalling the midplane assemblyRemoving a compute sledRemoving a st

Página 74

Next steps1. Install the following:• interposer module(s)• fan interface board, if applicable• PCIe modules and PCIe switch board, if applicable• cool

Página 75

Steps1. Remove the Mylar insulator.2. Disconnect the power bus bar and the cable cover from the midplane assembly.3. Disconnect the power bus bar and

Página 76 - Power interposer board

Steps1. Place the power interposer board in the carrier.2. Install the four screws to secure the power interposer board to the carrier.3. Reconnect th

Página 77

Figure 60. Removing and installing the cable tube1. control panel 2. screw (5)3. cable tube 4. control panel cable3. Remove the screw that secures the

Página 78 - Control panel

Sled slot numberingFigure 1. Sled slot numbering—four-bay chassisFigure 2. Sled slot numbering—eight-bay chassisFigure 3. Sled slot numbering—two-bay

Página 79

Next stepsInstall the control panel.Related LinksInstalling the control panelInstalling the control panelPrerequisitesCAUTION: Many repairs may only b

Página 80 - KVM panel

NOTE: You must remove the KVM panel to replace a faulty panel.1. Ensure that you read the Safety instructions.2. Follow the procedure listed in Before

Página 81

Figure 63. Removing and installing the KVM panel1. screw 2. KVM panel cable3. connector 4. KVM panel5. KVM panel coverNext stepsInstall the KVM panel.

Página 82 - Installing the KVM panel

6. Insert the KVM panel cable in the cable tube.7. Align the screw holes on the cable tube with the screw holes on the side of the system.8. Install t

Página 83

5Troubleshooting your systemNOTE: This chapter provides troubleshooting information for the PowerEdge FX2 and FX2s enclosures only. For troubleshootin

Página 84 - Troubleshooting your system

If the tests fail, see Getting Help.Troubleshooting enclosure componentsThe following procedures describe how to troubleshoot the enclosure components

Página 85

NOTE: After installing a PSU, allow several seconds for the system to recognize the PSU and determine whether it is working properly.3. If the problem

Página 86 - Troubleshooting cooling fans

Troubleshooting expansion cardsPrerequisitesCAUTION: Many repairs may only be done by a certified service technician. You should only perform troubles

Página 87 - Troubleshooting I/O modules

Steps1. Check that the pass-through module or switch ports are cabled correctly.2. Ensure that the network daughter cards/LOM cards on the sleds are m

Página 88

6Technical specifications—PowerEdge FX2/FX2sEnclosure specificationsPhysical Height 8.68 cm (3.41 inch)Width 43.35 cm (17.06 inch) without rack ears48

Página 89 - FX2/FX2s

Figure 5. Sled slot numbering—three-bay chassisFront panel features and indicators—PowerEdge FX2/FX2sFigure 6. Front panel features and indicators—Pow

Página 90

Up to two PowerEdge FD332 storage sleds mapped to two PowerEdge FC630 compute sleds, orUp to two PowerEdge FD332 storage sleds mapped to up to four Po

Página 91

Enclosure control panelExternally accessible connectorsUSB One 4-pin, USB 1.1-compliant connector for keyboard and mouse support.Video 15-pin VGAI/O m

Página 92

EnvironmentalMaximum AltitudeOperating3,048 m (10,000 ft)Storage 12,000 m (39,370 ft).Operating Altitude De-ratingUp to 35 °C (95 °F) Maximum temperat

Página 93

Expanded operating temperatureNOTE: When operating in the expanded temperature range, system performance may be impacted.NOTE: When operating in the e