Dell Metered PDU LCD Manual do Utilizador Página 21

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 90
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 20
21
Installation
|
Attaching the Ground Wire
To attach the ground wire to the rack:
NOTE:
Dell recommends that you ground the rPDU to the rack frame with the ground wire provided in the Grounding Wire
Kit.
1 Connect one end of the ground wire to the ground bonding point location on the front panel of the rPDU
using the silver, 10-32
0.5 pan-head screw and star washer (supplied).
2 Connect the other end of the ground wire to a hole in the rack frame using the black, M5 12 pan-head
screw and star washer (supplied). See Figure 10.
Ground Bonding Point Connection
10-32
0.5” Pan-head Screw (Silver)
Star Washer
Frame Connection
M5
12 Pan-head Screw (Black)
Star Washer
Figure 10. Ground Bonding Point and Frame Connections
3 Continue to “Connecting Protected Equipment” on page 22.
Vista de página 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 89 90

Comentários a estes Manuais

Sem comentários